earth_america
user_standard Log on
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
How to

How to


Products: AS-B, Edge Server, Enterprise Central, Enterprise Server, Function Block Editor, AS-P, Virtual Project Servers
Functionalities: Programming, Engineering, User Management
Product version: 2024, 7.0
12/3/2024

Configuring a User Account Group to Only Use Classic Mode for Function Block Programs

You configure a user account group to only allow the use of classic function block editor and views and turn off the possibility to use Builder for Function Block.

To configure a user account group to only use classic mode for Function Block programs
  1. In WorkStation , in the System Tree pane, select the EcoStruxure BMS server.

  2. In the Control Panel tab, select Account management .

  3. In the Server list, select the EcoStruxure BMS server.

  4. In the Domain list, select the domain the user account group belongs to.

  5. In the User Account Groups list, select the user account group.

  6. Click Policies .

  7. Select “Only use classic mode for Function Block Programs”.

  8. Click Save .