The IP-IO module comes in three models with different I/O point count and different I/O point types.
The output override function allows you to manually override outputs. This function can be used for testing, commissioning, and maintenance of equipment.
RP and MP controllers and I/O modules are devices that have three types of memory:
IP-IO-UIO5DOFA4 has 9 I/O points and the IP-IO module is equipped with four pluggable terminal blocks and one fixed terminal block.
IP-IO-UIO10 has 10 I/O points and the IP-IO module is equipped with four pluggable terminal blocks.
IP-IO-DI10 has 10 I/O points and the IP-IO module is equipped with four pluggable terminal blocks.
The IP-IO module is delivered with terminal blocks installed on the device. The IP-IO module uses pluggable terminal blocks, which are easy to install and remove from the device.
The IP-IO module provides I/O expansion to your HVAC application over BACnet/IP and can share their I/O resources across applications running in automation servers, BACnet/IP controllers, or third-party systems. The IP-IO module can be installed near facilities in the field, away from the automation server or the BACnet/IP controller.
Use this workflow to commission one or more devices using the Zero Friction Commissioning function in the Commission mobile application. Related information can be found in the section after the flowchart.