A user account group has the permission Full Access to the Enterprise Server and No Access to the Servers folder on the Enterprise Server. A single user account has Full Access permissions to Automation Server 1, but No Access to Automation Servers 2 and 3. The No Access permission on the Servers folders makes it possible to give specific user accounts access to specific Automation Servers in that folder.
The path permission rules rely on the actual path string with the name of the SmartStruxure server or folder. If you change the name of a SmartStruxure server or folder, users that earlier had permission are denied access. For example, a user group has full access to the folder LABB. The folder is renamed to Laboratory B. The users that had access to the LABB folder do not have access to the Laboratory B folder or its subfolders.
The local admin account is always granted access on the local SmartStruxure server. Für weitere Informationen siehe Administration Accounts in SmartStruxure Server Local Domain .
The System folder and its subfolders, except the Domains folder, are always accessible to a user even when the path permission for the folders is set to No Access. This means that a user can always at least navigate and view the objects in the System Tree and its subfolders.
The Domains folder is the only folder within the System folder with restricted access for users with the path permission No Access.