Use this workflow to activate licenses offline. Offline activation is typical used when Device Administrator and the SmartX servers are not connected to the Internet. Related information can be found in the sections after the flowchart.
In Device Administrator, create the request files.
Para obtener más información, consulte Creating the Request Files .
Upload the request files to FlexNet Operations Administrator server. After the files are processed, you download the response files to activate the licenses on the SmartX servers.
Para obtener más información, consulte Uploading the Request Files and Downloading the Response Files .
In Device Administrator, send the response files to the SmartX server to complete the license activation.
Para obtener más información, consulte Sending the Response Files to the SmartX Server .
After the licenses has been installed, make a backup of the SmartX server to make sure that you do not lose the licenses if the SmartX server crashes.
Para obtener más información, consulte Backup .