Use this workflow to activate licenses offline. Offline activation is typically used when Device Administrator and the automation servers are not connected to the Internet. Related information can be found in the sections after the flowchart.
In Device Administrator, create the request files.
Per maggior informazioni, consulta Creating the Request Files .
Using Device Administrator, activate request files on License Activation Server (FNO) to receive response files. To be able to complete this procedure, you must be on a computer that is connected to License Activation Server (FNO) via the Internet, and have Device Administrator installed.
Per maggior informazioni, consulta Activating Request Files to Receive Response Files .
Using Device Administrator, send the response files to the automation server to complete the license activation.
Per maggior informazioni, consulta Sending the Response Files to the Automation Server .
After the licenses has been installed, make a backup of the automation server to make sure that you do not lose the licenses if the automation server crashes.
Per maggior informazioni, consulta Backup .