earth_america
user_standard Log on
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
Concept

Concept


Products: Operator Display
Functionalities: Engineering, BACnet/IP devices
Product version: 3.3, 2022, 2023, 2024, 7.0
7/22/2021

BACnet Objects

BACnet objects and devices have a variety of required and optional properties that are used for the purposes of identification, reliability indication, and configuration of the object or device, and for prioritization of write requests.

The supported BACnet objects in Operator Display are:

  • Analog Input Object Type

  • Analog Output Object Type

  • Analog Value Object Type

  • Binary Input Object Type

  • Binary Output Object Type

  • Binary Value Object Type

  • Device Object Type

  • Multi-State Input Object Type

  • Multi-State Output Object Type

  • Multi-State Value Object Type

Analog Object Type Properties

Input

Output

Value

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Units

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Units

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Units

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Binary Object Type Properties

Input

Output

Value

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Inactive_Text

Active_Text

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Inactive_Text

Active_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Inactive_Text

Active_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Multi-State Object Type Properties

Input

Output

Value

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Number_of_States

State_Text

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Number_of_States

State_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

Description

Event_State

Number_of_States

State_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

  • Configuration
  • Device Discovery Detail Screen
  • Alarm Detail Screen
  • Inputs/Analog Detail Screen
  • Inputs/Binary Detail Screen
  • Inputs/Multi-State Detail Screen
  • Outputs/Analog Detail Screen
  • Outputs/Binary Detail Screen
  • Outputs/Multi-State Detail Screen
  • Values/Analog Detail Screen
  • Values/Binary Detail Screen
  • Values/Multi-State Detail Screen