0
概念

概念


产品: Operator Display
功能: 工程, SmartX IP Controller 设备
产品版本: 3.3, 2022, 2023, 2024, 7.0
2021/9/10

BACnet 对象

BACnet 对象和设备具有各种必需和可选属性,用于对象或设备的标识、可靠性指示和配置,以及写入请求的优先级排序。

操作员显示中支持的 BACnet 对象包括:

  • 模拟输入对象类型

  • 模拟输出对象类型

  • 模拟值入对象类型

  • 二进制输入对象类型

  • 二进制输出对象类型

  • 二进制值对象类型

  • 设备对象类型

  • 多态输入对象类型

  • 多态输出对象类型

  • 多态值对象类型

模拟对象类型属性

输入

输出

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

单元

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

单元

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

单元

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Binary Object Type Properties

输入

输出

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Inactive_Text

Active_Text

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Inactive_Text

Active_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Inactive_Text

Active_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

多态对象类型属性

输入

输出

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Number_of_States

State_Text

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Number_of_States

State_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

Object_Identifier

Object_Name

Object_Type

Present_Value

描述

Event_State

Number_of_States

State_Text

Priority_Array

Relinquish_Default

Acked_Transitions

Event_Time_Stamps

Event_Message_Texts_Config

  • 配置
  • 设备发现详情屏幕
  • 报警详情屏幕
  • 输入/模拟详细信息屏幕
  • 输入/二进制详情屏幕
  • 输入/多状态详情屏幕
  • 输出/模拟详情屏幕
  • 输出/二进制详情屏幕
  • 输出/多态详情屏幕
  • 值/模拟详情屏幕
  • 值/二进制详情屏幕
  • 值/多态详情屏幕