您可以在趋势图中添加实时趋势系列,以比较不同日志或变量中的趋势数据。

显示更多
action_close

In a trend chart, a series can be presented as a line, discrete line, digital, or bars. In a trend chart, series can be presented in different colors and with different line weights.

In WorkStation, in a multi trend log list, series are presented as text and can be exported to .XML or .CSV.

 
action_zoom_plus_stroke Types of series presentation, schematic
图: Types of series presentation, schematic

To make reading easier in a trend chart, records can be presented with markers. Markers can only be shown for lines and discrete lines, not for digital or bars.

 
action_zoom_plus_stroke Presentation with markers, schematic
图: Presentation with markers, schematic

如要在趋势图中添加实时趋势系列
  1. 在工作站的 系统树 窗格中,选择要添加趋势系列的趋势图。 ​

  2. 文件 菜单中,点击 属性

  3. 系列配置设置 下,点击 添加 按钮

     
    action_zoom_plus_stroke

     
    action_zoom_plus_stroke
  4. 在对象类型列表中,选择 实时趋势系列

     
    action_zoom_plus_stroke
  5. 名称 框中,键入系列的名称。

  6. 描述 框中,键入系列的描述。

     
    action_zoom_plus_stroke
  7. 点击 下一个

  8. 显示变量 框中,输入要在趋势图中显示的变量的路径。

     
    action_zoom_plus_stroke
  9. 粗细 框中,输入系列的线条粗细。

  10. 显示标记 框中,选择 以显示每个记录的值的标记。

     
    action_zoom_plus_stroke
  11. 点击 创建

     
    action_zoom_plus_stroke
  12. 点击 确定