You save a backup set from an automation server to another location so you can store the backup set on, for example, a network drive or a USB memory.
In WorkStation, on the Tools menu, click Control Panel .
On the Control Panel toolbar, select the EcoStruxure BMS server.
Click Backup Sets .
In the List View , open the Local folder for an automation server or the AS Archives folder for an Enterprise Server.
If connected to the Enterprise Server, open the automation server folder that contains the backup set.
Select the backup set that you want to save to a different location.
On the Actions menu, click Save To .
In the Save As dialog box, enter a storage location and click Save .
Click Close .