earth_america
user_standard Zaloguj się
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
Poradnik

Poradnik


Produkty: AS-B, Enterprise Central, Enterprise Server, AS-P, WorkStation, Project Configuration Tool
Funkcje: Harmonogramy
Wersja produktu: 3.2, 3.3, 2022
2020-10-15

Deleting a Date List Entry from a Calendar

You delete a date list entry from a calendar to remove the entry from a schedule.

To delete a date list entry from a calendar
  1. In WorkStation, in the System Tree pane, select the calendar.

  2. In the work area, click the Calendar Editor view.

  3. In the Date List , select an entry.

  4. On the Calendar Editor toolbar, click the Delete button

     
    action_zoom_plus_stroke
    .

Repeat the procedure to delete additional date list entries.

  • Calendar Editor Overview
  • Calendar Editor Toolbar