Displaying Trend Log List Values as Bitstrings

You present trend log list values as bitstrings.

显示更多
action_close

A trend log list displays all values in the trend log in a list.

You can create a trend log list directly from a trend log and refresh the values.

You can manually add records to a trend log list for any type of trend log.

Trend Log List Display

A trend log list can be displayed in a number of ways.

有关更多信息,请参阅 Trend Log List Display .

Export of Trend Log Lists and Records

Trend log lists and records can be exported in two different formats:

  • CSV

  • XML

有关更多信息,请参阅 Export of Trend Log Lists and Records .

 
action_zoom_plus_stroke Trend log list
图: Trend log list

To display trend log list values as bitstrings
  1. In WorkStation, in the System Tree , select the trend log list values you want to display as bitstrings

  2. On the Trend Log List toolbar, click the Show values as bitstrings button

     
    action_zoom_plus_stroke
    .

The values in the trend log list are now shown as bitstrings.

  • How Trend Logs Work
  • Trend Log Lists in WorkStation
  • Opening a Trend Log List
  • Refreshing a Trend Log List
  • Displaying Trend Log List Values as Decimals
  • Exporting a Trend Log List to XML format
  • Exporting a Trend Log List to CSV Format
  • Trend Log List Toolbar
  • Trend Log List Event Icons