SmartStruxure Server Device Replacement Using Restore Workflow

Use the workflow to duplicate the SmartStruxure server device from a backup set.

 
action_zoom_plus_stroke Duplicate SmartStruxure server device using restore flowchart
Abbildung: Duplicate SmartStruxure server device using restore flowchart
Copy SmartStruxure server device Backup Set to WorkStation

Save the most current backup set of the SmartStruxure server device that you want to replace to WorkStation.

Für weitere Informationen siehe Saving a SmartStruxure Server Device Backup Set to Another Location .

Add new SmartStruxure server device to network and configure communication settings

Add the new SmartStruxure server device to the network and configure the IP address.

Für weitere Informationen siehe Configuring a SmartStruxure Server Device to Use DHCP .

Für weitere Informationen siehe Setting the SmartStruxure Server Device IP Address .

Log on to SmartStruxure server device using WorkStation

Für weitere Informationen siehe In WorkStation als Building Operation-Benutzer einloggen .

Import backup set

Import the backup set to the new SmartStruxure server device.

Für weitere Informationen siehe Importing a Backup Set to SmartStruxure Server Device .

Restore new SmartStruxure server device using the imported Backup Set

Restore the new SmartStruxure server device using the imported backup set.

Für weitere Informationen siehe Restoring the SmartStruxure Server .

Hinweis

If the SmartStruxure server device does not go online, you can manually recreate the SmartStruxure server device or restore the connections between the Enterprise Server and the SmartStruxure server device. Für weitere Informationen siehe SmartStruxure Server Device Remains Offline After Restore .

The Restore process automatically renames the SmartStruxure server device and specifies the objects and properties that the SmartStruxure server device uses to reestablish links and go online.

  • Restore
  • SmartStruxure Server Device Replacement Using Restore
  • Backup Sets
  • Saving a SmartStruxure Server Device Backup Set to Another Location
  • Configuring a SmartStruxure Server Device to Use DHCP
  • Setting the SmartStruxure Server Device IP Address
  • In WorkStation als Building Operation-Benutzer einloggen
  • Importing a Backup Set to SmartStruxure Server Device
  • Restoring the SmartStruxure Server
  • SmartStruxure Server Device Remains Offline After Restore