earth_america
user_standard Iniciar sesión
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
Concepto

Concepto


Productos AS-B, Edge Server, AS-P, Project Configuration Tool
Funcionalidades: Funcionalidad básica
Versión del producto: 2023, 2024
17/12/2022

Automation Server Replacement Using Restore Workflow

Use the workflow to duplicate the automation server from a backup set.

 
action_zoom_plus_stroke Duplicate automation server using restore flowchart
Figura: Duplicate automation server using restore flowchart
Copy automation server Backup Set to WorkStation

Save the most current backup set of the automation server that you want to replace to WorkStation.

Para obtener más información, consulte Saving an Automation Server Backup Set to Another Location .

Add new automation server to network and configure communication settings

Add the new automation server to the network and configure the IP address.

Para obtener más información, consulte Configuring an Automation Server to Use DHCP .

Para obtener más información, consulte Configuring the Automation Server IP Address .

Log on to automation server using WorkStation

Para obtener más información, consulte Inicio de sesión en WorkStation como usuario de EcoStruxure Building Operation .

Import backup set

Import the backup set to the new automation server.

Para obtener más información, consulte Importing a Backup Set to Automation Server .

Restore new automation server using the imported Backup Set

Restore the new automation server using the imported backup set.

Para obtener más información, consulte Restoring the EcoStruxure BMS Server .

Aviso

If the automation server does not go online, you can manually recreate the automation server or restore the connections between the Enterprise Server and the automation server. Para obtener más información, consulte Automation Server Remains Offline After Restore .

The Restore process automatically renames the automation server and specifies the objects and properties that the automation server uses to reestablish links and go online.

  • Restore
  • Automation Server Replacement Using Restore
  • Backup Sets
  • Saving an Automation Server Backup Set to Another Location
  • Configuring an Automation Server to Use DHCP
  • Configuring the Automation Server IP Address
  • Inicio de sesión en WorkStation como usuario de EcoStruxure Building Operation
  • Importing a Backup Set to Automation Server
  • Restoring the EcoStruxure BMS Server
  • Automation Server Remains Offline After Restore