Use the workflow to duplicate the field server from a backup set.
Save the most current backup set of the field server that you want to replace to WorkStation.
Mer information finns i Saving a Field Server Backup Set to Another Location .
Add the new field server to the network and configure the IP address.
Mer information finns i Configuring a Field Server to Use DHCP .
Mer information finns i Configuring the Automation Server IP Address .
Mer information finns i Logging on to WorkStation as an EcoStruxure Building Operation User .
Import the backup set to the new field server.
Mer information finns i Importing a Backup Set to Field Server .
Restore the new field server using the imported backup set.
Mer information finns i Restoring the EcoStruxure BMS Server .
If the field server does not go online, you can manually recreate the field server or restore the connections between the Enterprise Server and the field server. Mer information finns i Field Server Remains Offline After Restore .
The Restore process automatically renames the field server and specifies the objects and properties that the field server uses to reestablish links and go online.