Use the workflow to duplicate the SmartX server from a backup set.
Save the most current backup set of the SmartX server that you want to replace to WorkStation.
有关更多信息,请参阅 Saving a SmartX Server Backup Set to Another Location .
Add the new SmartX server to the network and configure the IP address.
有关更多信息,请参阅 Configuring a SmartX Server to Use DHCP .
有关更多信息,请参阅 Configuring the SmartX Server IP Address .
有关更多信息,请参阅 以 EcoStruxure Building Operation 用户身份登录 WorkStation .
Import the backup set to the new SmartX server.
有关更多信息,请参阅 Importing a Backup Set to SmartX Server .
Restore the new SmartX server using the imported backup set.
有关更多信息,请参阅 Restoring the EcoStruxure BMS Server .
If the SmartX server does not go online, you can manually recreate the SmartX server or restore the connections between the Enterprise Server and the SmartX server. 有关更多信息,请参阅 SmartX Server Remains Offline After Restore .
The Restore process automatically renames the SmartX server and specifies the objects and properties that the SmartX server uses to reestablish links and go online.