Restoring Licenses Administrated by License Administrator

You restore the license data from a backup to restore a corrupt or non-functioning License Server.

Mehr zeigen
action_close

Backup the license files on a regular basis. To back up the license files, copy all files in the folder to an external resource. Backups are useful if the hardware or the operating system malfunctions.

Backed up licenses can only be restored on the same License Server that the files were backed up from. If you plan to move the licenses to another License Server, you first must return the licenses to the License Activation Server and then activate them on the new License Server. Für weitere Informationen siehe Return Licenses Administrated by License Administrator .

The license files are located in: \ProgramData\FLEXnet in Windows.

The restored licenses files may on rare occasions be considered damaged by the License Server. If so, they must be repaired. Für weitere Informationen siehe EcoStruxure Building Operation Software License Repair .

To restore licenses administrated by License Administrator
  1. Close all EcoStruxure Building Operation software that requires license.

  2. ​On the computer that runs License Server, browse to the the folder \ProgramData\FLEXnet\

  3. Paste all your backed up files to the FLEX-net folder.

    Hinweis

You now restart the License Server so you can check out the restored licenses. Für weitere Informationen siehe Restarting the License Server .

  • Backing Up Licenses Administrated by License Administrator
  • Repairing an EcoStruxure Building Operation Software License
  • Restarting the License Server
  • Licenses Administrated by License Administrator Backup and Restore
  • Problem with the Licenses on the License Server