earth_america
user_standard Iniciar sessão
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
Como

Como


Produtos: License Administrator, License Server
Funcionalidades: Gestão de licenças
Versão do produto: 3.2, 3.3, 2022, 2023, 2024
15-07-2020

Restoring EcoStruxure Building Operation Software Licenses

You restore the license data from a backup to restore a corrupt or non-functioning License Server.

Mostrar mais
action_close

Backup the EcoStruxure Building Operation software license files on a regular basis. To back up the license files, copy all files in the folder to an external resource. Backups are useful if the hardware or the operating system malfunctions.

Backed up licenses can only be restored on the same License Server that the files were backed up from. If you plan to move the licenses to another License Server, you first must return the licenses to the License Activation Server and then activate them on the new License Server. Para mais informações, consulte EcoStruxure Building Operation Software License Return .

The license files are located in: \ProgramData\FLEXnet in Windows.

The restored licenses files may on rare occasions be considered damaged by the License Server. If so, they must be repaired. Para mais informações, consulte EcoStruxure Building Operation Software License Repair .

To restore EcoStruxure Building Operation software licenses
  1. Close all EcoStruxure Building Operation software that requires license.

  2. ​On the computer that runs License Server, browse to the the folder \ProgramData\FLEXnet\

  3. Paste all your backed up files to the FLEX-net folder.

    Nota

You now restart the License Server so you can check out the restored licenses. Para mais informações, consulte Restarting the License Server .

  • Backing Up EcoStruxure Building Operation Software Licenses
  • Repairing an EcoStruxure Building Operation Software License
  • Restarting the License Server
  • EcoStruxure Building Operation Software License Backup and Restore
  • Problem with the Licenses on the License Server
  • EcoStruxure Building Operation Software Requirements