You edit an exception event to change the time range, start and stop date, start and stop time, or weekdays of an exception event.
You cannot add, edit, or delete schedule events in a Xenta Schedule when a Xenta Central schedule has been assigned to it.
The number of events a Xenta Central schedule can have is determined by the Menta application.
In WebStation, in the System Tree pane, select the schedule containing the exception event you want to edit.
In the Interval type column, edit Interval , On all day or Off all day .
Edit the dates.
Click Save .
To delete an exception event, click the trash can.