You synchronize WebReports with a deployed report to ensure that the report displays in the WebReports Reports Tree. You use WebReports with a Web browser to complete this procedure.
If you have added images to your report, synchronization alone will not enable you to see them in the deployed report. To see newly added or changed image(s), you must redeploy each time you add or change an image.
Log on to WebReports with an administrator's user account.
In WebReports, on the menu bar, select Report Packs .
On the Manage Report Packs page, click Synchronize .
When synchronization is successful, click OK .
Verify that the new folder and the report are in the Reports Tree.
Now, you can generate and view the new report from a Web browser or in WorkStation.