earth_america
user_standard Log on
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
How to

How to


Products: Enterprise Central, Enterprise Server, FDP Server
Functionalities: Security
12/3/2024

Enabling Web Server Access Logging

You enable web server access logging to log all web server HTTP access.

Show More
action_close

You can log all web server HTTP access to the Enterprise Server and the Enterprise Central.

The log on traffic is logged in the httpaccess.log file at the following locations:

  • Enterprise Server:

    C:\ProgramData\Schneider Electric EcoStruxure\Building Operation x.y\Enterprise Server\db\logs

  • Enterprise Central:

    C:\ProgramData\Schneider Electric EcoStruxure\Building Operation x.y\Enterprise Central\db\logs

The log is not created until you enable web server access logging.

To enable web server access logging
  1. In WorkStation, in the System Tree pane, select the EcoStruxure BMS server you want to configure.

  2. Click the Control Panel tab.

  3. Click Security Settings .

  4. In the Security Manager , select Enable web server access logging .

  5. Click the Save button

     
    action_zoom_plus_stroke
    .

  • Web Server Access Logging
  • Control Panel Tab