This section provides the RJ45 pinout for the RP-C controller's two RS-485 ports.
The RS-485 ports are labelled Sensor Bus (RS-485 Com A) and Room Bus (RS-485 Com B). For more information, see RP-C Communication Ports . The RJ45 pinout is identical for the two RS-485 ports.
|
RJ45 Pin |
Description |
|
1 |
Not connected |
|
2 |
Not connected |
|
3 |
RS485+ (A) |
|
4 |
+24 VDC |
|
5 |
Ground |
|
6 |
RS485– (B) |
|
7 |
+24 VDC |
|
8 |
Ground |
The wiring recommendations for the RS-485 ports depend on the type of network the ports are used for. For more information, see Communication Port Wiring .