Concept

Concept


Products: AS-P Smoke Control, Automation Server Smoke Control
Functionalities: Smoke Control
Product version: 1.8
9/26/2016

UL 864 Smoke Control Enclosure Mounting Hardware

You should ensure that you have the proper diameter mounting hardware and anchoring system before mounting the UL 864 Smoke Control enclosures.

Mounting hardware may vary depending on the surface in which the enclosures are anchored:

  • When anchoring directly to a support member, such as a stud, use diameter mounting hardware 0.25-inch (or M6 metric) screws

  • When achoring to concrete, brick, and mortar, use expansion anchors

  • When anchoring to thin walls (drywall or hollow wall), use toggle and threaded anchors

Important:

Check the hardware manufacturer's maximum recommended weight-bearing loads before choosing your mounting hardware.

Table: Enclosure Weight

Model

Weight

MNA-FLO-1

5 lbs (2 kg)

UNM-SCH13186RC

20 lbs (9 kg)

UNM-SCH181810RC

30 lbs (13 kg)

UNM-SCH242410RC

50 lbs (22 kg)

UNM-SCH243610RC

60 lbs (27 kg)

UNM-SCH303610RC

80 lbs (36 kg)

UNM-SCH304810RC

100 lbs (45 kg)