The RP-C controller comes in six different models, which offer five different combinations (sets) of I/O point types and CPU types. Four of the RP-C controller models support 24 VAC/DC input power and two of the models support 230 VAC.
RP-C 24 V controller models:
RP-C-12A-F-24V, RP-C-12B-F-24V, RP-C-12C-F-24V, and RP-C-16B-F-24V
RP-C 230 V controller models:
RP-C-16A-F-230V and RP-C-16B-F-230V
Range |
Model |
I/O–CPU Set |
I/O Points |
CPU Type |
RAM / Flash Memory |
Input Power |
Advanced |
RP-C-12A-F-24V
|
12A |
12 |
ARM Cortex-A7 single-core
|
6 MB / 48 MB |
24 VAC at 50/60 Hz or 24 to 30 VDC |
Advanced |
RP-C-12B-F-24V |
12B |
12 |
ARM Cortex-A7 single-core
|
6 MB / 48 MB |
24 VAC at 50/60 Hz or 24 to 30 VDC |
Advanced |
RP-C-12C-F-24V |
12C |
12 |
ARM Cortex-A7 single-core
|
6 MB / 48 MB |
24 VAC at 50/60 Hz or 24 to 30 VDC |
Advanced |
RP-C-16A-F-230V |
16A |
16 |
ARM Cortex-A7 single-core
|
6 MB / 48 MB |
230 VAC at 50/60 Hz |
Pro |
RP-C-16B-F-24V |
16B |
16 |
ARM Cortex-A7 dual-core
|
128 MB / 64 MB |
24 VAC at 50/60 Hz or 24 to 30 VDC |
Pro |
RP-C-16B-F-230V |
16B |
16 |
ARM Cortex-A7 dual-core
|
128 MB / 64 MB |
230 VAC at 50/60 Hz |
Więcej informacji zawiera RP-C Onboard I/O .
Więcej informacji zawiera RP-C Built-in Power Supply .
All RP-C models have the same small footprint.
There are a number of differences in hardware between different hardware versions of the RP-C-12A-F-24V, RP-C-12B-F-24V, RP-C-12C-F-24V, and RP-C-16A-F-230V controller models.
Więcej informacji zawiera Differences Between RP-C Hardware Versions .