You can reset the administrator password on your EcoStruxure Building Operation servers. Related information can be found in the sections after the flowchart.
In Device Administrator, set the Enterprise Server, Enterprise Central and automation server in reset mode.
Für weitere Informationen siehe Setting an EcoStruxure BMS Server to Password Reset Mode .
In Project Configuration Tool, set the Project Configuration Tool server in reset mode.
Für weitere Informationen siehe Setting an EcoStruxure PCT Server in Password Reset Mode .
In WorkStation, copy the session ID that you need to get a temporary password.
Für weitere Informationen siehe Copying the Session ID when Resetting the Password .
Contact your local Schneider Electric Buildings support team and send them the session ID.
Log on to the server using the temporary password supplied by Schneider Electric Buildings support team and create the new password.
Für weitere Informationen siehe Resetting the Password using WorkStation .