In the Write to File Notification Distribution Method, you sign the PDF notification report with a document signature certificate to add credibility to the report.
Make sure to select the option to convert your notifications to PDF and choose the signing option in the Write to File distribution method configuration. For more information, see Creating an Alarm Triggered Notification .
In WorkStation, in the System Tree pane, select the EcoStruxure BMS server you want to configure.
Click the Control Panel tab.
Click Certificates .
In the Certificates tab, in the Server list, select the EcoStruxure BMS server in which you want to use a certificate.
In the Document Signature Certificate list, chose the certificate you want to use.