earth_america
user_standard 登录
action_search_stroke
earth_america
登录以评价并提供反馈 1 2 3 4 5 登录以评价
0
如何

如何


产品: AS-B, Edge Server, Enterprise Server, AS-P, WorkStation, Project Configuration Tool
功能: 趋势
产品版本: 2024, 7.0
2024/12/3

Adding a Trend Log Series to a Trend Chart

You add a trend log series to a trend chart to compare trend data from different logs or variables.

显示更多
action_close

In a trend chart, a series can be presented as a line, discrete line, digital, or bars. In a trend chart, series can be presented in different colors and with different line weights.

In WorkStation, in a multi trend log list, series are presented as text and can be exported to .XML or .CSV.

 
action_zoom_plus_stroke Types of series presentation, schematic
图: Types of series presentation, schematic

To make reading easier in a trend chart, records can be presented with markers. Markers can only be shown for lines and discrete lines, not for digital or bars.

 
action_zoom_plus_stroke Presentation with markers, schematic
图: Presentation with markers, schematic

To add a trend log series to a trend chart
  1. In WorkStation, in the System Tree pane, select the trend chart you want to add a trend log series to. ​

  2. In the System Tree pane, select the trend log you want to add.

  3. Drag the trend log from the System Tree pane to the trend chart diagram.

  4. Click Save .

  • Trend Series
  • Trend Chart Event Icons
  • Removing a Trend Chart Series
  • Trend Chart View