AD v2 uses a wired (USB) connection to communicate with EcoStruxure BMS servers. During installation and commissioning, you can use a wireless access point to establish communication between AD v2 and EcoStruxure BMS servers. AD v2 can be powered either by a AS-P server, AS-B server, or USB power adapter.
Communication over a USB Connection
The preinstalled AD-Link application enables AD v2 to communicate with EcoStruxure BMS servers over a USB connection.
When AD v2 is connected to a AS-P server or AS-B server, AD v2 can be powered by the automation server through the USB cable. The screen must not be turned on constantly because this may drain the battery.
Nota
|
LOSS OF DATA OR POWER
Use only USB cables ordered from Schneider Electric.
Use only USB cables that are designed for AD.
Do not use USB cables that exceed 3 m (10 ft).
Failure to follow these instructions can result in loss of data or power.
|
action_zoom_plus_stroke
Imagem:
USB connection to a AS-P server or AS-B server