You edit the path permissions of an individual user account or of a user accountgroup to modify the access the user account or the user account group is granted to EcoStruxure Building Operation software.
In WorkStation, in the System Tree pane, select the EcoStruxure BMS server you want to configure.
Click the Control Panel tab.
Click Account management .
In the account management control panel, in the Domain list box, select the domain the user account or the user account group belongs to.
In the User Accounts list box or the User Account Groups list box, select the user account or the user account group, you want to edit path permissions.
Click Software permissions .
In the Permissions tab, in the Path list, select the path for which you want to edit the permissions.
In the permissions column, select a set of permission.
In the Properties column click on the Property Permissions icon
In the Property Permissions dialog box, select the level of permission you want to assign to various properties. Per maggior informazioni, consulta Property Permissions Dialog Box .
Click OK .
The Property Permissions icon
Click the Save button