Use the workflow to duplicate the SmartX server from a backup set.

 
action_zoom_plus_stroke Duplicate SmartX server using restore flowchart
Figura: Duplicate SmartX server using restore flowchart
Copy SmartX server Backup Set to WorkStation

Save the most current backup set of the SmartX server that you want to replace to WorkStation.

Para obtener más información, consulte Saving a SmartX Server Backup Set to Another Location .

Add new SmartX server to network and configure communication settings

Add the new SmartX server to the network and configure the IP address.

Para obtener más información, consulte Configuring a SmartX Server to Use DHCP .

Para obtener más información, consulte Configuring the SmartX Server IP Address .

Log on to SmartX server using WorkStation

Para obtener más información, consulte Inicio de sesión en WorkStation como usuario de EcoStruxure Building Operation .

Import backup set

Import the backup set to the new SmartX server.

Para obtener más información, consulte Importing a Backup Set to SmartX Server .

Restore new SmartX server using the imported Backup Set

Restore the new SmartX server using the imported backup set.

Para obtener más información, consulte Restoring the EcoStruxure BMS Server .

Aviso

If the SmartX server does not go online, you can manually recreate the SmartX server or restore the connections between the Enterprise Server and the SmartX server. Para obtener más información, consulte SmartX Server Remains Offline After Restore .

The Restore process automatically renames the SmartX server and specifies the objects and properties that the SmartX server uses to reestablish links and go online.

  • Restore
  • SmartX Server Replacement Using Restore
  • Backup Sets
  • Saving a SmartX Server Backup Set to Another Location
  • Configuring a SmartX Server to Use DHCP
  • Configuring the SmartX Server IP Address
  • Inicio de sesión en WorkStation como usuario de EcoStruxure Building Operation
  • Importing a Backup Set to SmartX Server
  • Restoring the EcoStruxure BMS Server
  • SmartX Server Remains Offline After Restore