Use the workflow to duplicate the automation server from a backup set.
Save the most current backup set of the automation server that you want to replace to WorkStation.
Pour plus d'informations, voir Saving an Automation Server Backup Set to Another Location .
Add the new automation server to the network and configure the IP address.
Pour plus d'informations, voir Configuring an Automation Server to Use DHCP .
Pour plus d'informations, voir Configuring the Automation Server IP Address .
Pour plus d'informations, voir Connexion à WorkStation en tant qu'utilisateur EcoStruxure Building Operation .
Import the backup set to the new automation server.
Pour plus d'informations, voir Importing a Backup Set to Automation Server .
Restore the new automation server using the imported backup set.
Pour plus d'informations, voir Restoring the EcoStruxure BMS Server .
If the automation server does not go online, you can manually recreate the automation server or restore the connections between the Enterprise Server and the automation server. Pour plus d'informations, voir Automation Server Remains Offline After Restore .
The Restore process automatically renames the automation server and specifies the objects and properties that the automation server uses to reestablish links and go online.