Automation Server Replacement Using Restore Workflow

Use the workflow to duplicate the automation server from a backup set.

 
action_zoom_plus_stroke Duplicate automation server using restore flowchart
Figura: Duplicate automation server using restore flowchart
Copy automation server Backup Set to WorkStation

Save the most current backup set of the automation server that you want to replace to WorkStation.

Per maggior informazioni, consulta Saving an Automation Server Backup Set to Another Location .

Add new automation server to network and configure communication settings

Add the new automation server to the network and configure the IP address.

Per maggior informazioni, consulta Configuring an Automation Server to Use DHCP .

Per maggior informazioni, consulta Configuring the Automation Server IP Address .

Log on to automation server using WorkStation

Per maggior informazioni, consulta Accesso a WorkStation come utente di EcoStruxure Building Operation .

Import backup set

Import the backup set to the new automation server.

Per maggior informazioni, consulta Importing a Backup Set to Automation Server .

Restore new automation server using the imported Backup Set

Restore the new automation server using the imported backup set.

Per maggior informazioni, consulta Restoring the EcoStruxure BMS Server .

Avviso

If the automation server does not go online, you can manually recreate the automation server or restore the connections between the Enterprise Server and the automation server. Per maggior informazioni, consulta Automation Server Remains Offline After Restore .

The Restore process automatically renames the automation server and specifies the objects and properties that the automation server uses to reestablish links and go online.

  • Restore
  • Automation Server Replacement Using Restore
  • Backup Sets
  • Saving an Automation Server Backup Set to Another Location
  • Configuring an Automation Server to Use DHCP
  • Configuring the Automation Server IP Address
  • Accesso a WorkStation come utente di EcoStruxure Building Operation
  • Importing a Backup Set to Automation Server
  • Restoring the EcoStruxure BMS Server
  • Automation Server Remains Offline After Restore