Use this workflow to upgrade an Enterprise Server system. An Enterprise Server system can include an Enterprise Server, one or more automation servers and WorkStations, and supporting administrator software, such as Device Administrator.
The workflow applies to a fully supported upgrade path.
Per maggior informazioni, consulta System Upgrade Overview
.
Prepare for Upgrade
Prior to upgrading a system, complete the tasks listed in the following flowchart. Related information can be found in the sections after the flowchart.
action_zoom_plus_stroke
Figura:
Pre-upgrade flowchart
Stop Reporting Agent Windows service
If you are upgrading WebReports, stop the Reporting Agent Windows service.
Per maggior informazioni, consulta Stopping the Reporting Agent Windows Service
.
Perform a system backup
Perform a new
All data
backup of the Enterprise Server and the automation servers when backing up the system.
Per maggior informazioni, consulta Backing Up EcoStruxure BMS Servers Manually
.
For systems that include a Reports Server, back up the WebReports database.
Per maggior informazioni, consulta Backing Up the WebReports Database
.
Stop License Server Windows service
Use the Services tool to stop the License Server Windows service.
Per maggior informazioni, consulta Stopping the License Server
.
Upgrade the EcoStruxure Building Operation Software
The following flowchart shows the tasks for upgrading the EcoStruxure Building Operation software, except automation servers. Related information can be found in the sections after the flowchart.
action_zoom_plus_stroke
Figura:
General upgrade flowchart
Upgrade License Server and License Administrator
Upgrade the License Server and License Administrator.
Per maggior informazioni, consulta Upgrading the License Administrator and the License Server
.
Upgrade Device Administrator
Upgrade the Device Administrator.
Per maggior informazioni, consulta Upgrading the Device Administrator Installation
.
Set up a Database Schema in the PostgreSQL Database
If you have an External Log Storage to store records using PostgreSQL and TimescaleDB you must set up a database schema in the PostgreSQL Database.
Per maggior informazioni, consulta Setting up a Database Schema in the PostgreSQL Database
.
Upgrade the Enterprise Server database
Install the Enterprise Server and select
Upgrade current version to
.
Per maggior informazioni, consulta Upgrading the Enterprise Server
.
Avviso
If a newer version of Enterprise Server already is installed, ensure that the Enterprise Server Windows service of this version is stopped.
Avviso
The Enterprise Server Windows service automatically restarts after the Enterprise Server upgrade is complete. If the Enterprise Server Windows service does not start, restart the computer.
Install WebStation language pack
If you want to use a language pack in WebStation, install the language pack and change the language setting in WebStation.
Per maggior informazioni, consulta Adding a Language in WebStation
.
Per maggior informazioni, consulta Modifica delle impostazioni regionali dell'utente
.
Upgrade WorkStations
Upgrade WorkStation and select the editor tools and language packs you want to upgrade.
Per maggior informazioni, consulta Upgrading WorkStation and Client Tools Installation
.
Avviso
Keep one WorkStation at an earlier version corresponding to the EcoStruxure BMS servers in case you need to make any engineering on the servers.
Upgrade automation servers
The following flowchart shows the tasks for upgrading automation servers. Related information can be found in the sections after the flowchart.
action_zoom_plus_stroke
Figura:
Automation server upgrade flowchart
Install certificates
When you upgrade from 2.0 to a higher version, you must install certificates to establish a trusted chain between the computer running Device Administrator and the automation servers. A trusted chain increases the security of your system and must be used if you use HTTPS.
If you upgrade from 3.0 to a higher version and have already established the trusted chain with certificates, no further action is needed.
Per maggior informazioni, consulta Device Administrator Certificate Workflow
.
Per maggior informazioni, consulta Automation Server Licensing Overview
.
Upgrade the automation server database
Use the upgraded Device Administrator to upgrade the databases of the automation servers using the IP network or USB port.
Per maggior informazioni, consulta Uploading and Upgrading an Automation Server
.
Open the Device Administrator upgrade log to get detailed information about the automation server upgrade process.
Per maggior informazioni, consulta Opening the Upgrade Log
.
Avviso
You can postpone the upgrade in the fully supported upgrade path of some automation servers.
Per maggior informazioni, consulta System Upgrade Overview
.
Open the conversion log and the high priority conversion log
Open the two conversion logs to see warning and error messages that occurred when the databases were upgraded.
Use Device Administrator to open the conversion log.
Per maggior informazioni, consulta Opening the Conversion Log
.
In Windows, open the high priority conversion log.
Per maggior informazioni, consulta Opening the High Priority Conversion Log
.
Fix configuration issues in automation server
Determine if you can use the converted database for download or if you need to fix configuration issues in the automation server and perform a new upgrade of the automation server database.
Per maggior informazioni, consulta Conversion Logs
.
Per maggior informazioni, consulta Log Entry Interpretation
.
Download the upgraded database
When you are comfortable with the content of the high priority conversion log, use Device Administrator to download the upgraded database to the automation server.
Per maggior informazioni, consulta Downloading an Upgraded Database to an Automation Server
.
Reset and Confirm Server Functions
The following flowchart shows the tasks for confirming the functions of the EcoStruxure BMS servers. Related information can be found in the sections after the flowchart.
action_zoom_plus_stroke
Verify control and monitoring operations
Use the Software Administrator (or the Services tool) to verify that the Enterprise Server Windows service is running.
Per maggior informazioni, consulta Starting the Enterprise Server or Enterprise Central Windows Service
.
In WorkStation, verify that the control and monitoring operations of the Enterprise Server are functioning normally per the guidelines specified for your site.
Avviso
In the Security Certificate Risk dialog box, click
Trust certificate
to temporarily trust the certificate and log on to the EcoStruxure BMS server.
Check for invalid or unresolved bindings for each automation server
In Binding Diagnostics, check for invalid or unresolved bindings.
Per maggior informazioni, consulta Checking the Status of Bindings
.
Replace any invalid or unresolved bindings with new bindings, using the Bindings view.
Per maggior informazioni, consulta Bindings Management
.
Avviso
The system may require 10 to 30 minutes to complete the process of resolving invalid or unresolved bindings. Wait for this process to finish before editing the bindings.
Install and activate certificates
In WorkStation, generate, add, and activate certificates for the EcoStruxure BMS servers.
Per maggior informazioni, consulta Generating a Certificate
.
Per maggior informazioni, consulta Adding a Certificate
.
Per maggior informazioni, consulta Activating a Certificate
.