earth_america
user_standard Accedi
action_search_stroke
earth_america
Log on to rate and give feedback 1 2 3 4 5 Log on to rate
0
Modalità

Modalità


Prodotti: AS-B, Edge Server, Enterprise Central, Enterprise Server, AS-P, Project Configuration Tool
Funzionalità: Gestione dell'utente
Versione del prodotto: 2023
16/12/2022

Preventing Users from Changing Their Passwords

You prevent a group of users from changing their passwords.

Mostra di più
action_close

As a WorkStation administrator, you can change users’ passwords, force users to change their passwords at next logon, or enable and disable the possibility for users to change their passwords.

Passwords are managed at the user account group level. EcoStruxure Building Operation software applies password changes to all user accounts that belong to the user account group.

Avviso
  • If you are an administrator and have forgotten your password, contact the EcoStruxure BMS support team.

To prevent users from changing their passwords
  1. In WorkStation, in the System Tree pane, select the EcoStruxure BMS server you want to configure.

  2. Click the Control Panel tab.

  3. Click Account management .

  4. In the Domain list box, select the domain the user account group belongs to.

  5. In the User Account Groups list box, select the user account group.

  6. Click Policies .

  7. In the Policies tab, clear the May change Password box.

  8. Click the Save

     
    action_zoom_plus_stroke
    button.

  • Software Permissions, User Accounts, and User Account Groups
  • Control Panel Tab
  • User Account Group – Policies Tab
  • Allowing Users to Change their Password
  • Password Administration