Use this workflow to assign and activate licenses on automation servers that do not have any access to Internet.
Related information can be found in the sections after the flowchart.
Install certificates if you use HTTPS for communication.
Per maggior informazioni, consulta Device Administrator Certificate Workflow .
Make sure that you have the Entitlements containing the licenses. You need the email with the entitlement during the process.
Per maggior informazioni, consulta Order Information Request .
In Device Administrator, you add entitlements that contains products and licenses.
This is done so that you can view all licenses that are available to be assigned and then activated.
Make sure that you have the HTML entitlement certificate file or the entitlement ID available .
There are two different procedures to add and set up an entitlement:
When the HTML entitlement certificate file is available.
Per maggior informazioni, consulta Adding an Entitlement using the HTML file when Automation Server is not Connected to License Server (FNO) .
When the HTML entitlement certificate file is not available you must use the entitlement ID.
Per maggior informazioni, consulta Adding an Entitlement without the HTML file when Automation Server is not Connected to License Server (FNO) .
Use the License Products available in the entitlements to assign License Features to the automation servers.
Per maggior informazioni, consulta Assigning Licenses .
In Device Administrator, create the request files.
Per maggior informazioni, consulta Creating the Request Files .
Using Device Administrator, activate request files on License Activation Server (FNO) to receive response files. To be able to complete this procedure, you must be on a computer that is connected to License Activation Server (FNO) via the Internet and have Device Administrator installed.
Per maggior informazioni, consulta Activating Request Files to Receive Response Files .
Using Device Administrator, send the response files to the automation server to complete the license activation.
Per maggior informazioni, consulta Sending the Response Files to the Automation Server .
After the licenses has been installed, make a backup of the automation server to make sure that you do not lose the licenses if any problems occur.
Per maggior informazioni, consulta Backup .