You log on to an Enterprise Server to restore an automation server.
In WorkStation, in the System Tree pane, select the automation server that you want to restore.
On the Actions menu, click Restore .
Take manual control of any output points that could potentially damage equipment before restoring the automation server. If you cannot disconnect the physical outputs, restore the automation server using a trusted restore file that will turn off/on the outputs predictably and safely.
In the Restore Options dialog box, in the Available restore points list, select a backup set in black text, which indicates that the backup set is compatible with the current version of the automation server.
Select the type of data you want to restore:
Select Configuration only to back up only configuration and custom object types data.
Select All data (Configuration and Historical) to back up the configuration, historical, and custom object types data.
Click Restore .
Click Yes .
Click Close .
After a restore, WorkStation may display several automation server events in the Events pane that occurred while the restore was taking place. However, these events are not part of the restored log data.