Use this workflow with the eCommission SmartX Controllers mobile application to check out I/O following the installation and wiring of MP Series controllers and other devices. Complete the tasks listed in the following flowchart. Information related to each task can be found in the sections following the flowchart.
Physically wire together the MP Series controllers and other devices that are to be connected.
Connect the eCommission application to the MP Series controllers.
Para obtener más información, consulte Opciones de arquitectura y conexión .
Start the eCommission application and log in, and then discover MP Series controllers on the network.
Para obtener más información, consulte Downloading and Starting the eCommission SmartX Controllers Mobile Application .
For each MP Series controller, perform checkout of its inputs and outputs.
Para obtener más información, consulte Realización de una comprobación E/S .
After connecting and checking out the MP Series controllers, you can proceed to other tasks as needed:
Capture device information from the controllers
Para obtener más información, consulte Capturing a Device with the Asset List Creator .